ISO Class 5 certified clean room environment. ESD-safe & zero-emission surfaces.
Drag the slider handle left and right to inspect the exact substrate condition before treatment versus the final engineered handover. Click either badge to view full screen.
After • Final Handover
Before • Original State
The existing floor lacked ESD protection and proper coving, creating contamination risks in critical vaccine preparation zones.
The completed clean room floor system meets all ISO Class 5 particulate standards and provides reliable ESD protection for sensitive biologic production.
Floor In adheres to strict ASTM substrate profiling, moisture barrier application, and conductive grounding protocols on every job site. Click any photo to view in full resolution.
Dust-free diamond grinding with HEPA-filtered extraction to achieve CSP-3 profile while maintaining cleanroom air standards.
Comprehensive substrate resistivity mapping and moisture vapor emission rate testing in accordance with ASTM F1869.
Application of water-based conductive epoxy primer with copper grounding tape grid connected to building earth points.
Installation of 100mm prefabricated radius coves forming a seamless transition from floor to wall for GMP compliance.
Application of 2mm self-leveling ESD epoxy with point-to-point resistance of 10^6 to 10^9 ohms per IEC 61340-5-1 standards.
Our certified engineering consultants evaluate your substrate, measure ambient moisture, and engineer the optimal chemical-resistant epoxy or polyurethane system.